Cooler Master V Series 550 W Review 13

Cooler Master V Series 550 W Review

EMC Pre-Compliance Testing »

Ripple Measurements

You will see the ripple levels we measured on the rails in the following table. The limits are, according to the ATX specification, 120 mV (+12V), and 50 mV (5V, 3.3V, and 5VSB).

Ripple Measurements - Cooler Master V550
Test12 V5 V3.3 V5VSBPass/Fail
10% Load9.3 mV4.5 mV13.9 mV3.9 mVPass
20% Load9.3 mV5.1 mV15.5 mV4.2 mVPass
30% Load10.4 mV4.9 mV16.5 mV4.9 mVPass
40% Load12.1 mV5.4 mV18.4 mV5.2 mVPass
50% Load14.3 mV5.9 mV18.8 mV5.5 mVPass
60% Load16.4 mV6.1 mV19.1 mV6.1 mVPass
70% Load18.7 mV6.4 mV20.9 mV6.9 mVPass
80% Load20.3 mV6.6 mV22.4 mV7.3 mVPass
90% Load21.9 mV7.2 mV22.8 mV7.6 mVPass
100% Load24.7 mV7.8 mV25.6 mV11.4 mVPass
110% Load27.0 mV8.3 mV26.4 mV9.2 mVPass
Crossload 111.9 mV5.8 mV17.9 mV4.7 mVPass
Crossload 225.1 mV8.0 mV24.4 mV7.7 mVPass

Ripple suppression at +12V, 5V and 5VSB was great and good-enough at 3.3V. Although it didn't do poorly, the 3.3V rail is this PSU's weak link considering its average overall performance.

Ripple at Full Load

You can see the AC ripple and noise the main rails registered (+12V, 5V, 3.3V, and 5VSB) in the following oscilloscope screenshots. The bigger the fluctuations on the oscilloscope's screen, the bigger the ripple/noise. We set 0.01 V/Div (each vertical division/box equals 0.01 V) as the standard for all measurements.



Ripple at 110% Load



Ripple at Crossload 1



Ripple at Crossload 2

Next Page »EMC Pre-Compliance Testing
View as single page
Aug 27th, 2024 22:24 EDT change timezone

New Forum Posts

Popular Reviews

Controversial News Posts