FSP Hydro G Series 750 W Review 3

FSP Hydro G Series 750 W Review

EMC Pre-Compliance Testing »

Ripple Measurements

You will see the ripple levels we measured on the rails in the following table. The limits are, according to the ATX specification, 120 mV (+12V) and 50 mV (5V, 3.3V, and 5VSB).

Ripple Measurements - FSP HG750
Test12 V5 V3.3 V5VSBPass/Fail
10% Load27.3 mV6.3 mV7.3 mV9.7 mVPass
20% Load21.0 mV5.9 mV9.6 mV10.7 mVPass
30% Load20.1 mV7.2 mV10.4 mV12.6 mVPass
40% Load17.0 mV7.6 mV11.8 mV14.5 mVPass
50% Load18.4 mV8.5 mV12.4 mV16.0 mVPass
60% Load18.7 mV8.8 mV13.6 mV18.2 mVPass
70% Load19.1 mV10.2 mV15.2 mV19.4 mVPass
80% Load19.3 mV11.4 mV16.6 mV21.6 mVPass
90% Load19.9 mV12.4 mV17.7 mV21.7 mVPass
100% Load21.6 mV13.0 mV19.9 mV21.9 mVPass
110% Load22.4 mV13.0 mV21.3 mV22.9 mVPass
Crossload 118.7 mV11.2 mV11.5 mV8.7 mVPass
Crossload 221.2 mV13.1 mV20.2 mV15.6 mVPass
Ripple suppression was excellent at +12V and 5V and good enough at 3.3V and 5VSB. With 10% load, ripple on the +12V rail is increased because the main switchers operate in PWM mode at light loads, only to switch into FM mode with higher loads.

Ripple at Full Load

You can see the AC ripple and noise the main rails registered (+12V, 5V, 3.3V, and 5VSB) in the following oscilloscope screenshots. The bigger the fluctuations on the oscilloscope's screen, the bigger the ripple. We set 0.01 V/Div (each vertical division/box equals 0.01 V) as the standard for all measurements.



Ripple at 110% Load



Ripple at Crossload 1



Ripple at Crossload 2